Conformity to RoHS Directive  
EMC Filters for AC Power Line  
For Triple-phase, Large-size Box Cased ZACT-ME Series  
FEATURES  
SAFETY STANDARDS  
Standard and standard No.  
• While reducing the filter size, the highly efficient thermal design  
allows the handling of large currents with high attenuation.  
• They are highly effective at preventing both the radiation and  
penetration of EMC noise. The parts are, therefore, highly  
immune to externally generated noise and do not, themselves,  
serve as sources of radiated noise  
U.S.A.  
Canada  
Europe  
NEMKO  
Part No.  
CSA  
UL  
UL1283  
CSA C22.2 No.8  
LR76849C  
EN60939  
P08208997  
ZACT2230-ME  
• For the frequency band set by CISPR, attenuation is shown for  
both differential mode and common mode noise components.  
• Can withstand voltages of AC.1250V between the lines, and AC.  
2000V between the line to ground.  
• It is a product conforming to RoHS directive.  
APPLICATIONS  
Computers, HDDs, electronic exchange devices, NC control  
devices, inverters for motor, etc.  
SHAPES AND DIMENSIONS  
K
øH  
R2  
S2  
T2  
R1  
S1  
T1  
B
F
J
C
D
Dimensions in mm  
Part No.  
ZACT2230-ME  
• Case: metal, terminal: stud  
A
120  
B
200  
C
115  
D
260  
E
100  
F
220  
øG  
M6  
H
5.5  
I
64  
J
66  
K
240  
ELECTRICAL CHARACTERISTICS  
Part No.  
ZACT2230-ME  
Rated voltage Eac(V)  
Rated current(A)  
250  
30  
Test voltage Eac(V)[Between terminal and case]  
Insulation resistance(M)  
[DC. 500V, 1min/between terminal and case]  
Leakage current(mA)[250V • 60Hz]  
DC resistance(m)  
2000  
100min.  
1max.  
40max.  
–25 to +85  
45  
Operating temperature range(°C)[Including self-temperature rise]  
With derating over(°C)  
Temperature rise(°C)  
35max.  
0.15 to 10  
0.15 to 10  
5
Differential mode at 40dB  
Common mode at 40dB  
Attenuation frequency range  
(MHz)[+5 to +35°C]  
Weight(kg)  
• Conformity to RoHS Directive: This means that, in conformity with EU Directive 2002/95/EC, lead, cadmium, mercury, hexavalent chromium, and specific  
bromine-based flame retardants, PBB and PBDE, have not been used, except for exempted applications.  
• All specifications are subject to change without notice.  
005-01 / 20090226 / e9111_zact_me.
 

Taylor Scale THD100 User Manual
Thermaltake Computer Hardware CLP0537 User Manual
TIC Speaker AS P25 User Manual
Toshiba Flat Panel Television TZ50V61 User Manual
Toshiba Projection Television 62HM116 User Manual
Toshiba Tablet PDA0EU00401Y User Manual
Troy Bilt Chipper CS 4310 User Manual
Uniden Headphones BTS200 User Manual
Unitron Hearing Aid Oxygen Equipment UMIC User Manual
Viking Speaker System 25AE User Manual